Multifamily Buildings Energy Standards Report

One 31-unit apartment building modeled under the IECC, ASHRAE 90.1, PHI Classic, PHI Low Energy Building, and Phius in climate zones 1 to 7, normalized to a common basis: Passive House cut heating and cooling demand and total energy two- to four-and-a-half-fold.

Key points

  • The differences between the IECC, ASHRAE, Phius, and PHI standards.
  • How Passive House standards compare with code minimum and other performance pathways.
  • The workflow for translating Passive House models to hourly simulation for a fair comparison.
  • How the choice of software and protocol affects reported results.